LA 716 силовой модуль - HS 716 система управления нагревом

The LA 716 provides 16 channels for switching resistive loads. Up to 650 W can be used per output channel.

Дизайн

  • Connection of heat radiation devices over 8-pole front connector (not included in scope of supply →see documentation)
  • Mains infeed over 3-pole terminal (Lx/N/Ly) on the front
  • 16 channel fuses in accessible holders
  • Cooling is possible using an optional fan unit

Функции

Output power

  • 16 power channels, each 230 V (8 outputs per phase)
  • Up to 650 W switching capacity per output with 100% concurrence
  • Up to 10400 W switching capacity per module
  • Zero-crossing power triacs
  • Protection of triacs and opto-triacs by transil diodes against overvoltage

Forced ventilated

Depending on the switching capacity and ambient temperature, the power output may require forced ventilation. For this purpose, an optional fan unit is available as an accessory (see accessories). For further details, see the manual.

Temperature monitoring

For monitoring the heat-sink temperature, there is an NTC thermistor on the heat sink. In the event of overheating, this temperature dependent resistor outputs an alarm to the higher-level control system.

Fuses

For each channel of the LA 716, a 5 A fusible link for protection of the power triacs is accessible externally. A safety cover is provided for protection against finger touch.

Diagnostic capability

Diagnostic functions are available as standard for detecting the following faults:

  • Triac circuit-breaker, high-resistance or fused junction
  • Channel fuse on module defective
  • External fault such as fuse rupture, break in radiation device or wire

Технические данные

Supply voltage

for control section

provided internally over the bus module

Power outputs

Number per power output

16

Galvanic isolation

 
  • to control section

through opto-triac and opto-coupler which are specified in acc. with VDE 0884

  • between power outputs

No

Load voltage

 
  • Rated value

230 V AC

  • Permissible range

187 ... 264 V (TN network)

  • Frequency

50/60 Hz (47 ... 63 Hz)

Output voltage

full-wave switched at zero crossover

Output current per channel

 
  • Rated value

2.82 A

  • Permissible range

0.1 ... 2.82 A

  • Residual current

≤ 10 mA

Maximum switching power per channel without ventilation and with ventilation (rate of flow ≥ 2 m/s)

650 W at 230 V

Loads

 
  • Load type

Resistive load with a maximum of 15-times the cold current in the first half-wave

  • Overload

Five-times rated current for 20 ms

Protective measures

 
  • Thermal monitoring

Yes (through NTC thermistor)

  • Short-circuit protection

One 5 A/250 V F fuse per output

  • Overvoltage protection

Yes

Connecting cables

 
  • Resistance

max. 14 Ohm
(to guarantee short-circuit protection)

  • Length

100 m unshielded
500 m shielded

Mechanical data

Dimensions W x H (mm)

237 x 233.4

Degree of protection to DIN 40050

IP00


Дополнительно

Description

Type

Manufacturer

Manufacturer Type No.

Siemens Type No.

Replacement fuse for power module

F5AH250V

Littelfuse

216005.MA000

200021116

230 V fan unit with 3 fans

On request

Rittal

On request

On request

8-pole, terminal strip with screw terminals

SLT 5.08/8B SN OR

Weidmüller

1611770000

On request