ENG: Measuring setups with remote seals
Installation

Remote seals of sandwich design are fitted between the connection flange of the measuring point and a dummy flange. Remote seals of flange design are fitted directly on the connection flange of the measuring point. The respective pressure rating of the dummy flange or the flanged remote seal must be observed.

The pressure transmitter should be installed below the connection flange (and below the lower connection flange in the case of differential pressure transmitters). This arrangement must be used in the low-pressure range.

When measuring at pressures above atmospheric, the pressure transmitter can also be installed above the connection flange.

The capillaries between the remote seal and the pressure transmitter should be as short as possible to obtain a good transmission response.

Offset of measuring range

If there is a difference in height between the two connection flanges when measuring with two remote seals, an additional differential pressure will result from the oil filling of the remote seal capillaries. This results in a measuring range offset which has to be taken into account when you set the pressure transmitter.

An offset in the measuring range also occurs when combining a remote seal with a transmitter if the remote seal is not installed at the same height as the transmitter.

Pressure transmitter output

If the level, separation layer or density increase in closed vessels, the differential pressure and hence the output signal of the pressure transmitter also increase.

For an inverted relationship between the differential pressure and the output signal, the start-of-scale and full-scale values of the SITRANS P must be interchanged.

With open vessels, a rising pressure is usually assigned to an increasing level, separation layer or density.

Influence of ambient temperature

Temperature differences between the individual capillaries and between the individual remote seals should be avoided.

Temperature variations in the area of the measuring setup cause a change in volume of the filling liquid and hence measuring errors.

Notes
  • For the separation layer measurement, the separation layer has to be positioned between the two spigots. Also you must make sure that the level in the container is always above the top spigot.
  • When measuring density, make sure that the level of the medium remains constant. The level should be above the top spigot.
Possible combinations of pressure transmitters and remote seals

Type of installation

Pressure transmitters

Remote seals

A/B

7MF40107MF40337MF40347MF40357MF80237MF8024

7MF49007MF49107MF4920

C1 and C2

7MF42337MF42347MF4235

7MF49007MF49107MF4920

(vacuum-proof design in each case)

 

7MF43337MF43347MF4335

7MF49017MF4921

D

7MF44337MF44347MF4435

7MF49037MF4923

E

7MF44337MF44347MF4435

7MF4913

G, H and J

7MF44337MF44347MF4435

7MF49037MF4923

 


Чертеж

ENG: Measuring setups with remote seals
Types of installation for pressure and level measurements (open vessels)
Types of installation for absolute level measurements (closed vessels)
Type of installation for differential pressure and flow measurements
Types of installation for level measurements (closed vessels)