| Case sizes and frame sizes | Case size (inverter) CS B: 0.37 kW to 1.5 kW CS C: 2.2 kW/3.0 kW | Frame size (motor) 71 M to 90 S/L 90 L/100 L |
| Input frequency | 47 Hz to 63 Hz |
| Output frequency | 0 Hz to 650 Hz (standard) |
| Power factor | ≥ 0.95 |
| Inverter efficiency | 94 % to 97 % at maximum power |
| Overload capability | Overload current 1.5 x rated output current (i.e. 150 % overload capability) for 60 s, cycle time 300 s |
| Inrush current | < 4 A for CS B and < 7.7 A for CS C |
| Control method | linear V/f characteristic, quadratic V/f characteristic, multipoint characteristic (parameterizable V/f characteristic), flux current control (FCC) |
| Pulse frequency | 4 kHz (standard) 2 kHz to16 kHz (in 2 kHz steps– with derating) |
| Fixed frequencies | 7, programmable |
| Skip frequency bands | 4, programmable |
| Setpoint resolution | 0.01 Hz digital 0.01 Hz serial 10 bit analog |
| Digital inputs (only with PROFIBUS module) | 2, programmable |
| Analog inputs (only with PROFIBUS module) | 1 for setpoint or PI input (0 to 10 V), scalable or for use as 3rd digital input |
| Relay output (only with PROFIBUS module) | 1 programmable, DC 24 V/0.5 A (resistive load) |
| Serial interface | RS 232 |
| Electromagnetic compatibility | EMC filter integrated to EN 55 011 Class A (radiated emissions: Class A) |
| Braking | DC braking, Compound braking: EM module (electromechanical brake control module) and REM module (resistor and electromechanical brake control module) available as options |
| Degree of protection | IP65 |
| Operating temperature | –10 °C to+40 °C (50 °C with derating) |
| Storage temperature | –40 °C to+70 °C |
| Relative humidity | 99 % (non-condensing) |
| Standard paint finish (motor) | Special paint finish in RAL 7030 stone grey |
| Installation altitude | up to 1000 m above sea level without derating |
| Protection features | - undervoltage
- overvoltage
- overload
- short circuit
- stall prevention
- motor overtemperature I2t, PTC
- inverter overtemperature
- parameter interlocking
|
| Conformance with standards | CE |
| CE-labeled | Complies with the European low-voltage directive 73/23/EEC and the electromagnetic compatibility directive 89/336/EEC |
| Dimensions (MICROMASTER 411 ECOFAST inverters only) | Case size (CS) CS B | Variant with PROFIBUS module PROFIBUS and EM module PROFIBUS and REM module AS-Interface module AS-Interface and EM module AS-Interface and REM module | H x L x W (mm) 212 x 246 x 224 212 x 246 x 274 212 x 246 x 337 212 x 246 x 224 212 x 246 x 274 212 x 246 x 337 | Weight, approx. (kg) 7.9 8.8 9.0 7.6 8.5 8.7 |
| | CS C | PROFIBUS module PROFIBUS and EM module PROFIBUS and REM module AS-Interface module AS-Interface and EM module AS-Interface and REM module | 247 x 279 x 247 247 x 279 x 297 247 x 279 x 360 247 x 279 x 247 247 x 279 x 297 247 x 279 x 360 | 10.4 11.3 11.5 10.1 11.0 11.2 |