4AP../4AU../4BU.. SIDAC-T transformersEach situation requires a suitable transformer to ensure the right voltage. SIDAC-T transformers are the right choice for each application: They are reliable and safe under different conditions worldwide.
Note: SITAS mains transformers with ≤ 50 V on the output side are always supplied as safety transformers. SIDAC-T transformers offer optimal protection with high permissible ambient air temperatures of up to 40 °C or 55 °C, high short-time rating for control transformers, fuseless construction, and the "Safety inside“ safety standard EN 61558. |
Особенности
|
Область примененияFor industrial machines, process engineering, heating and air-conditioning etc. and supplying control and signaling circuits if
Generally for converting voltages for electrical devices e.g. for communications technology, medical apparatus, and domestic appliances. The 4BU three-phase transformers are used for plant, switching, and control technology as well as for converting the local mains voltage to the operating voltage of the plant or its components. In addition, they limit the possible short-circuit currents. Power transformers with electrical isolation or autotransformers are used to convert the existing local voltages for machines and plants. In addition, power transformers can be used for electrical devices used for communications technology, medical apparatus, and domestic appliances. Special converter transformers are used in drive engineering for voltage conversion and autotransformers are used for infeed/feedback modules. |
Дизайн [PDF]Для просмотра информации в формате PDF необходимо установить Adobe Acrobat Reader. |
ДизайнRegulationsEN 61558-2-6, -2-4, -2-2, -2-1, -2-13, DIN VDE 0532-6 The German standard EN 61558 with the VDE classification VDE 0570 is the German edition of the international standard IEC 61558 (Safety of power transformers, power supply units and similar) and has fully replaced the previous standards VDE 0550 and VDE 0551. Some transformers are subjected to more stringent manufacturing and testing conditions in view of these changes. Transformers for general applications always have double or strengthened isolations for SELV voltages (exposed conductive parts, maximum AC 50 V or DC 120 V) i.e. these transformers are exclusively safety transformers. In addition, all transformers have been marked with information about safety elements which can be used to protect them against short-circuits and overloads. The SITAS transformer series contains the combined features of safety, isolating, control, and mains transformers, i.e. one transformer for (virtually) all applications. SITAS transformers fulfill the highest requirements (and with regard to safety the most stringent requirements) of the transformer designs contained in this catalog A SITAS transformer is always the right one for all applications. Rated power Pn for high ambient air temperatures – the characteristic for thermal ratingReference conditions under which the transformers can be subjected to the rated power Pn listed in the selection tables:
Other installation and operating conditions than this will affect the permissible continuous load capacity. If the ambient temperature is 30 °C, the 4AP transformers, for example, can operate with 8 % more load. (see load characteristic). Short-time rating Pn(S6) of control transformers – the characteristic variable for the dynamic capacityThe most important selection criterion for control transformers is their short-time rating Pn(S6). This is required for switching on electromagnetic loads, e. g. contactors with high making current in relation to holding current. According to EN 61558-2-2 "Special requirements for control transformers“ the output voltage with this load should not drop more than 5 % in relation to the rated voltage in order to ensure safe switching. Depending on their application, 4AP and 4AU control transformers ≤ 16 kVA are especially optimized for high short-time ratings with comparatively low ratings and thus small size. Low inrush current primary –side short-circuit and overload protection with standard circuit-breakersThe 4AP and 4AU three-phase transformers for the power range ≤ 16 kVA have been designed for protective devices which reliably protect the transformers against short-circuits or overloads. Standard 3RV and 3VF circuit-breakers offer optimum protection. In this way the transformers are protected on the primary side against both short-circuits and overload, without the possibility of nuisance tripping on startup. The low inrush current, the short-circuit current and the thermal load capacity on overload are matched to the tripping characteristics of the circuit-breakers. It is also possible to protect the transformers on the secondary side against short-circuits or overloads with circuit-breakers or miniature circuit-breakers with C characteristics. Note: The specified primary side circuit-breakers are for protecting the primary side of transformers in the event of short-circuits and overload on the secondary side. In the event of a possible short-circuit on the feeder lines between the protective device and the primary side of the transformer, the rated short-circuit breaking capacity of the circuit-breaker must be taken into account with regard to the maximum possible prospective short-circuit current at the place of installation. For device assignments, see table in the "Technical data". DesignAll 4AP, 4AU and 4BU three-phase transformers are supplied for screw mounting on a mounting plate. ConnectionsThe 4AP transformers are supplied for rated currents up to 60 A, the 4AU transformers for rated currents up to 43 A, and the 4BU transformers for rated currents up to 81 A in the standard design with screw-type terminals. For higher currents, the transformers are supplied with flat-type terminals or threaded pins. Enclosure mountingAll 4AP and 4AU SIDAC-T transformers can be supplied on request in protective enclosures to degree of protection IP23 and IP54, the 4BU transformers can be supplied on request in protective enclosures to degree of protection IP20 and IP23. Required specifications for requests and orders for 4AP, 4AU and 4BU special transformersRated power Pn (power separation for separate SEC coils, Pn = P1 + P2, throughput rating = consumer load for autotransformers), PRI and SEC voltages, frequency, vector arrangement, degree of protection (derating for other degrees of protection as IP00), Order No stem. The Order No. stem is added to the Order No. for the delivery. Order example: Special three-phase transformer 180 kVA PRI 415 V ± 5%, SEC 115 V, Frequency AC 50 Hz...60 Hz, Degree of protection IP00, Shield winding, Order No. stem 4BU60 32 (without UL), 4BU60 33 (with cURus) 4AU and 4BU autotransformers: Determining the type rating Pn typ.Thermistor transformer protection for 4BU special transformersThe windings of the thermistor transformers can be protected from impermissible overheating by means of thermistor transformer protection. Thermistors are used as temperature sensors. These are embedded in the windings at each limb of the transformer and connected in series. The rated response temperature is slightly above the limit temperature for continuous operation and in the event of a short-circuit. Possible designs:
The connections of the temperature sensors are connected to terminals, 2 terminals each for warning and disconnection. The 3RN tripping units are not included with the transformer, for selection and ordering data see "Timer, monitoring, coupling relays, and converters; Thermistor motor protection“. |
Технические данные [PDF]Для просмотра информации в формате PDF необходимо установить Adobe Acrobat Reader. |
Технические данные |
Характеристика |
Схема подключения [PDF]Для просмотра информации в формате PDF необходимо установить Adobe Acrobat Reader. |
Схема подключения
|